Voltage drop and cable size: circuit schedule with limits by standard, protection checks and report

List the circuits of a board, choose the standard, and see for each circuit the drop, the running total from the origin, the size that passes and why, then hand in the report.

What the tool does

Most voltage drop calculators take one circuit at a time and give a number without saying which limit applies or how it was worked out. The tool checks a whole schedule and shows the working.

How to use it

  1. Choose the standard and how the installation is supplied.
  2. Enter or paste the circuits, set "Fed from" for circuits on a sub-board, and leave the size on "Automatic" or choose one.
  3. In "Cable table", enter the ampacity for your installation method from your standard or the cable maker, with R, X or mV/A/m if you have them.
  4. Read the checks per circuit and change sizes, lengths or devices.
  5. Export the report PDF or the workbook.

What is built in and what you enter

Built in: the formulas, the conductor resistance of IEC 60228 class 2 conductors at 20 °C, the temperature coefficients of copper and aluminium, and the limit percentages of public documents with their clause. Not built in: the limits of 内線規程, and ampacity and correction factor tables. They belong to the standards bodies, so you enter the values from the edition you work to; the report names the table you used.

How it was checked

Before every release the engine is run on published worked examples: a three-phase 200 V, 40 A, 100 m run on 38 mm² cable with R 0.626 and X 0.0955 Ω/km at cos φ 0.85 gives 4.0 V, about 2.0 % (Fujikura-Dia); 17.8 × 200 m × 250 A / (1000 × 150 mm²) gives 5.93 V; 35.6 × 30 m × 20 A / (1000 × 2 mm²) gives 10.68 V; and 0.61 mV/A/m at 250 A over 100 m stays within 4 % of 415 V (Prysmian). The limits are tested clause by clause, and the protection checks with a small table.

Limits

The tool is for low-voltage circuits. It does not compute short-circuit currents, earth fault loop impedance, disconnection times, motor starting drop or harmonics, and it does not derive ampacity from the installation method. Check the design against the standard that applies and the cable maker's data.