Battery storage sizing: self-consumption, peak shaving and off-grid

Enter the consumption as monthly totals or open a meter file, add the PV from the solar tool, and simulate the year step by step for a battery size and operating mode. Compare capacities side by side and see what a peak limit really needs.

What the tool does

A battery is sized by what it changes over a whole year, not by one good day. The tool simulates every hour or every 15 minutes: PV first supplies the consumption, surplus charges the battery within its power and capacity, and the battery supplies the consumption when PV is short. It then reports what changed.

How to use it

  1. Enter the consumption: twelve monthly totals with a daily pattern (household, office, shop), or a meter file with 15-minute, 30-minute or hourly values in kWh, kW or W.
  2. Add the PV: open a project file saved by the PV string sizing and energy yield tool (with its weather data) or an hourly CSV with a column ac_w. A factor scales it to another array size.
  3. Set the battery: usable capacity, power, round-trip efficiency and lowest state of charge, and choose the operation.
  4. Enter your tariffs and battery prices to see savings and payback.
  5. Read Results and Days, compare capacities, check peak shaving or off-grid, and export the report, the workbook or the time series.

How it was checked

The simulation reproduces hand calculations exactly. With 1 kW of constant consumption and 3 kW of PV for four hours a day, a 10 kWh battery without losses cuts import from 20 to 12 kWh a day and raises self-sufficiency from 16.7 % to 50 %, with 292 full cycles a year; at 81 % round-trip efficiency the 8 kWh charged gives 6.48 kWh back. A load of 10 kW with two hours at 20 kW every day needs 10 kWh and 5 kW to stay under 15 kW, and the simulation holds the import at 15 kW with 12 kWh but not with 8 kWh. Fourteen such cases run before every release.

Limits

Monthly totals with a daily pattern are an estimate; peaks in particular need a meter file. Ageing, temperature, standby losses, time-of-use tariffs and grid charging for arbitrage are not modelled. Warranties, cycle limits, fire and installation rules and the utility's conditions decide what can be installed.